| Power supply : | Direct current |
| Working voltage : | 8.2 Vdc (1Kohm) |
| Switching distance (mm) : | 2 |
| Output type : | Namur |
| Hysteresis (%Sn) : | 1 ÷ 10 |
| Max. switching frequency : | 2000 Hz |
| Repeatability (%Sn) : | <= 3 |
| Current absorption at 8.2V : | Target detected <= 1 mA - Target not detected >= 3 mA |
| Led indicator : | Present |
| Operating temperature limits : | -25 ÷ +60 °C |
| Storage temperature limits : | -30 ÷ +70 °C |
| IP rating : | IP 67 |
| Housing material : | Nickelled brass |
| Weight : | 70 g |
| Mechanical characteristics : | M12x1 |
| Connection type : | H plug |
| Explosive atmosphere type : | Mixture Air/gas and/or Air/Dust |
| Equipment category : | 1G / 1D |
| Installation area : | Gas: Zone 0, Zone 1 and Zone 2 - Dust: Zone 20, Zone 21 and Zone22 |
| Protection method : | Intrinsically safe |
| Marking : | Gas: II 1G Ex ia IIC T6 Ga - Dust: II 1D Ex ia IIIC T85°C Da -25< Ta |
| Safety information : | Connection to certified intrinsically safe circuits only with the following values : Uo <= 17 V , |
| Conforming standard : | EN60079-0, EN60079-11 and EN60947-5-12 |
| EC-tipe examination certificate - ATEX : | IMQ 13 ATEX 019 |
| Certificate of conformity (CoC) - IECEx : | IECEx IMQ 13.0012X |