德国快速配送至全球

Lamtec BT300  BurnerTronic Image

Lamtec BT300 BurnerTronic


Product Name: Lamtec BT300 BurnerTronic
Brand: Lamtec
Product Code: BT300
Tags: Lamtec Lamtec BurnerTronic Lamtec BT300 BurnerTronic BT300 BurnerTronic BurnerTronic Lamtec BT300 Lamtec BT300 BurnerTronic BT300 BurnerTronic Lamtec BurnerTronic Lamtec BT300 BurnerTronic
BurnerTronic



您对制造商Lamtec的产品Lamtec BT300 BurnerTronic,代码为BT300感兴趣吗?立即联系我们获取报价。Imtek Engineering,世界上最快最可靠的工业设备供应商,将为您提供最佳报价!

Get Offer With E-Mail: info@im-tek.com
Get a offer for Lamtec BT300 BurnerTronic from our live support team now!

Power supply 2 30 V  +10/-15 %  47-63 Hz 120 V  +10/-15 %  47-63 Hz (on request) Maximum backup-fuse 10 A slow-blow   To be used only in a grounded power line network! Power consumption max. 30 VA Switching threshold of ionisation current 1 µ A Digital signal inputs Max. line length 10 m (33 ft)  Max. line length 20 m (66 ft) for the following signals:  Firing rate+ / firing rate-  Boiler safety interlock chain (SIC) Burner ON Reset  Alarm Fuel selection DFM   Digital outputs 3 fuel valves max. 1 A cos ? 0,4 VL fan max. 2 A cos ? 0,4  oil pump max. 2 A cos ? 0,4 ignition transformer max. 2 A cos ? 0,2  alarm output max. 1 A cos ? 0,3   Resolution 999 digit,  bit 10 Number of curve sets BT320/33x: 1 curve set (oil or gas) BT34x: 2 curve sets (oil/gas switchable; DFM300 or LCM100 required) Number of programs unlimited (EEPROM) Field bus-coupling (optional) PROFIBUS DP Modbus TCP PROFINET LEM100 or LCM100 always required Housing Polycarbonate + ABS Dimensions (HxWxD) 200x11 5x61 mm (7.87x4.53x2.4" in) Weight 1 ,0 kg (2.20 lb) Flammability UL-94 V0