Control unit for SIEMENS 8WL-6202 drive without aux. contactsThe type 8513 initiator unit is used for the power supply, remote control, function monitoring and switch position reporting of switch drive motors and operates on the 3- or 4-core cable principle (depending on the version).
Technical data | |
Dimensions | WxHxD 100/70/115 mm |
Housing | ABS / polystyrene |
Attachment | 2 holes to be drilled as per the drill- |
ing template, standard carrying rail | |
as per DIN EN 50022 | |
Type of protection | Housing: IP 40; terminals: IP 10 |
Ambient temperature | -20°C to +60°C |
Fuse | as required (as standard 6.3 A) |
Control buttons | 2 (for On and O?) |
Contact rating | max. AC 250 V; 5.0 A |
Message | 2 LEDs, colours: red, yellow, green |
according to the order details (de- | |
fault: “ON” = red, “OFF” = green) | |
per 1 zero-potential changeover | |
contact for “On” and “O?” respec- | |
tively U ? AC 250 V; I ? 2 A; | |
P ? 500 VA | |
Remote control con- | |
nection | |
Current drawn | approx. 250 mW |
Voltage | DC 24 V (19 - 34 V) |
? 8513 01 / ? 8513 11 | |
DC 60 V (38 - 86 V) | |
? 8513 02 / ? 8513 12 | |
DC 110 V (88 -120 V) | |
? 8513 03 / ? 8513 13 | |
Times | Pulse lengthening = runtime limiting |
default: approx. 10 s (can be set | |
from 1 s - 15 s) | |
Test voltage | Field side against reporting contacts |
and field side against actuation side | |
4 kVe? (1 minute) | |
4-core cable drive (with- | ? 8513 0- |
out pulse lengthening | |
and runtime limiting) | |
3-core cable drive (with | ? 8513 1- |
pulse lengthening and | |
runtime limiting) | |
Ordering information | |
Type | Part No. |
8513 01 | 310200 |
8513 11 | 310201 |
8513 02 | 310202 |
8513 12 | 310203 |
8513 03 | 310204 |
8513 13 | 310205 |
Control Unit