97% customer satisfaction based on last 45 days of sales
Order Processing & Delivery Information:
As we supply industrial equipment, product availability and delivery timelines may vary. Once your order is placed, our sales team will contact you within 24 business hours (excluding weekends and holidays) to confirm stock status and estimated delivery time.
Get the best price and fastest delivery for Hirschmann 9620154 Sp?der-Pl-20-08T1S29999Ty9 942141-029 from Hirschmann. Imtek Engineering offers worldwide industrial equipment supply with expert support.
| More Interfaces | |
| Power supply/signaling contact | 1 plug-in terminal block, 6-pin |
| USB interface | 1 USB for configuration |
| Network size - Length of cable | |
| Twisted pair (TP) | 0 - 100 m |
| Singlemode fiber (SM) 9/125 | 0 - 30 km (Link Budget at 1300 nm = 0 - 16 db; A = 0.4 dB/km; BLP = 3.5 ps/(nm*km)) |
| Network size - Cascadibility | |
| Line - / star topology | any |
| Power requirements | |
| Operating voltage | 12/24V DC (9.6 VDC - 32 VDC), redundant |
| Current consumption at 24 V DC | Max 200 mA |
| Power consumption | Max. 5 W, 16.9 Btu (IT)/h |
| Service | |
| Diagnostics | LEDs (power, link status, data, data rate) |
| Ambient conditions | |
| Operating temperature | -40 C to +70 C |
| Storage/transport temperature | -40 C to +85 C |
| Relative humidity (non-condensing) | 10 % to 95% |
| MTBF (Telecordia) | 954,743 hours |
| Mechanical construction | |
| Housing dimensions (w/o terminal block) W x H x D | 56mm x 135mm x 117mm |
| Mounting | DIN Rail |
| Weight | 510 g |
| Protection class | IP 40 |
| Mechanical stability | |
| IEC 60068-2-27 shock | 15 g, 11 ms duration, 18 shocks |
| IEC 60068-2-6 vibration | 3.5 mm, 5-8.4 Hz, 10 cycles, 1 octave/min; 1 g, 8.4-150 Hz, 10 cycles, 1 octave/min |
| EMC interference immunity | |
| EN 61000-4-2 electrostatic discharge (ESD) | 4 kV contact discharge, 8 kV air discharge |
| EN 61000-4-3 electromagnetic field | 10 V/m (80 - 1000 MHz) |
| EN 61000-4-4 fast transients (burst) | 2 kV power line, 4 kV data line |
| EN 61000-4-5 surge voltage | power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line |
| EN 61000-4-6 conducted immunity | 10 V (150 kHz - 80 MHz) |
| EMC emitted immunity | |
| FCC CFR47 Part 15 | FCC 47 CFR Part 15 Class A |
| EN 55022 | EN 55022 Class A |
| Approvals | |
| Basis Standard | CE, FCC, EN61131 |
| Safety of industrial control equipment | cUL61010-1/61010-2-201 |
| Scope of delivery | |
| Scope of delivery | device, terminal block, safety instruction |