| Product characteristics |
|---|
| Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Measuring range | |
| Process connection | threaded connection M18 x 1,5 internal thread |
| Application |
|---|
| Special feature | Gold-plated contacts |
| Measuring element | 1 x Pt 1000; (to DIN EN 60751, class B) |
| Media | liquids and gases |
| Pressure rating [bar] | 300 |
| Minimum installation depth [mm] | 15 |
| Electrical data |
|---|
| Operating voltage [V] | 20...30 DC |
| Current consumption [mA] | < 66 |
| Min. insulation resistance [M?] | 100; (500 V DC) |
| Protection class | III |
| Reverse polarity protection | yes |
| Power-on delay time [s] | 1.5 |
| Integrated watchdog | yes |
| Inputs / outputs |
|---|
| Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
| Outputs |
|---|
| Total number of outputs | 2 |
| Output signal | switching signal; analogue signal; (configurable) |
| Electrical design | PNP |
| Number of digital outputs | 1 |
| Output function | normally open / normally closed; (parameterisable) |
| Max. voltage drop switching output DC [V] | 2 |
| Permanent current rating of switching output DC [mA] | 250 |
| Number of analogue outputs | 1 |
| Analogue current output [mA] | 4...20 |
| Max. load [?] | 500 |
| Analogue voltage output [V] | 0...10 |
| Min. load resistance [?] | 2000 |
| Short-circuit protection | yes |
| Type of short-circuit protection | pulsed |
| Overload protection | yes |
| Measuring/setting range |
|---|
| Probe length L [mm] | 45 |
| Measuring range | |
| Set point SP | | -39.5...125 °C | -39...257 °F |
|
| Reset point rP | | -40...124.5 °C | -40...256 °F |
|
| Analogue start point | |
| Analogue end point | |
| In steps of | |
| Resolution |
|---|
| Resolution of switching output [K] | 0.5 |
| Resolution of analogue output [K] | 0.125 |
| Resolution of display [K] | 0.5 |
| Accuracy / deviations |
|---|
| Switch point accuracy [K] | ± (Pt 1000 + 0,2 K) |
| Precision analogue output [K] | ± (Pt 1000 + 0,2 K + 0,4%) |
| Display accuracy [K] | ± (Pt 1000 + 0,2 K + 1/2 Digit) |
| Temperature drift per 10 K [K] | 0.1 |
| Response times |
|---|
| Dynamic response T05 / T09 [s] | 1 / 3; (to DIN EN 60751) |
| Max. measuring/display cycle [ms] | 200 |
| Software / programming |
|---|
| Adjustment of the switch point | programming button |
| Parameter setting options | hysteresis / window; normally open / normally closed; min/max memory reset; Display unit; zero-point calibration; analogue output selectable and scalable |
| Operating conditions |
|---|
| Ambient temperature [°C] | -25...70 |
| Storage temperature [°C] | -40...100 |
| Protection | IP 67 |
| Tests / approvals |
|---|
| EMC | | DIN EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | | EN 61000-4-3 HF radiated | 10 V/m | | DIN EN 61000-4-4 Burst | 2 kV | | EN 61000-4-6 HF conducted | 10 V |
|
| Shock resistance | | DIN IEC 68-2-27 | 50 g (11 ms) |
|
| Vibration resistance | | DIN EN 60068-2-6 | 20 g (10...2000 Hz) |
|
| Mechanical data |
|---|
| Housing | compact type for adapter |
| Materials | stainless steel (1.4301 / 304); PBT; PC; EPDM/X; FKM |
| Materials (wetted parts) | stainless steel (1.4404 / 316L) |
| Process connection | threaded connection M18 x 1,5 internal thread |
| Displays / operating elements |
|---|
| Display | | switching status | LED, red | | function display | 7-segment LED display | | measured values | 7-segment LED display |
|
| Remarks |
|---|
| Remarks | | The values for accuracy apply to flowing water. |
|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | Connector: 1 x M12; Contacts: gold-plated |