| Switch temperature difference | 7K (±4K tolerance) |
|---|---|
| Sensor element | thermostatic bimetal |
| Contact type | snap-action contact |
| Service life | > 100,000 cycles |
| Max. operating voltage | AC 250 V (VDE) AC 120 V (UL) |
| Max. inrush current | AC 16 A for 10 sec. |
| Connection | 2-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm² (AWG 14) stranded wire1 1.5mm² (AWG 16) |
| Mounting | clip for 35mm DIN rail, EN 60715 |
| Casing | plastic according to UL94 V-0, light grey |
| Dimensions | 60 x 33 x 43 mm |
| Weight | approx. 40 g |
| Fitting position | variable |
| Operating/Storage temperature | -45 to +80 °C (-49 to +176 °F) |
| Operating/Storage humidity | max. 90 % RH (non-condensing) |
| Protection type | IP20 |
¹ When connecting with stranded wires, wire end ferrules must be used.
Important note: The contact system of the regulator is subjected to environmental influences, thus the contact resistance may change. This can lead to a voltage drop and/or self-heating of the contacts.
| Setting range | Art. No. Contact breaker (NC) | Art. No. Contact maker (NO) | Switching current/capacity max. | Approvals | |||||
|---|---|---|---|---|---|---|---|---|---|
| AC 250 V | AC 120 V | DC 24-72 V | |||||||
| 0 to +60 °C | 01140.0-00 | 01141.0-00 | 10 (2) A | 15 (2) A | 30 W | VDE | - | - | EAC |
| -10 to +50 °C | 01142.0-00 | 01143.0-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | - | EAC |
| +20 to +80 °C | 01159.0-00 | 01158.0-00 | 3 (2) A | 3 (2) A | 30 W | VDE | UL File No. E164102 | CSA | EAC |
| +32 to +140 °F | 01140.9-00 | 01141.9-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | CSA | EAC |
| +14 to +122 °F | 01142.9-00 | 01143.9-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | CSA | EAC |
| 0 to +60 °C | 01146.9-00 | 01147.9-00 | 10 (2) A | 15 (2) A | 30 W | VDE | UL File No. E164102 | CSA | EAC |
Thermostat