97% customer satisfaction based on last 45 days of sales
Order Processing & Delivery Information:
As we supply industrial equipment, product availability and delivery timelines may vary. Once your order is placed, our sales team will contact you within 24 business hours (excluding weekends and holidays) to confirm stock status and estimated delivery time.
Get the best price and fastest delivery for Gestra LRG16-4 from Gestra. Imtek Engineering offers worldwide industrial equipment supply with expert support.
Description
The conductivity electrode LRG 16-4 together with the conductivity switch LRS 1-.. or conductivity controller LRR 1-.. is
designed for measuring and monitoring electrical conductivity
in conductive fluids.
If used as conductivity limiter or continuous blowdown controller in steam boilers, the conductivity electrode LRG 16-4
can be used with the following equipment:
Conductivity switch LRS 1-50
Conductivity controller LRR 1-50
Conductivity controller LRR 1-52Technical data
Service pressure
PN 40, max. 32 bar at 238 °C
Mechanical connection
Screwed G 3/8 ISO 228-1
Materials
Screw-in body: 1.4571, X6CrNiMoTi17-12-2
Measuring electrode: 1.4571, X6CrNiMoTi17-12-2
Electrode rod insulation: PTFE
Length of measurement & installation
100, 300, 400, 500, 600, 800, 1000 and 1200 mm
Cell constant
1 cm-1
Electrical connection
Four-pole connector, cable glands M 16 (PG 11)
with integral cable clamp
Protection
IP 65 to DIN EN 60529
Admissible ambient temperature
Max. 70 °C
Weight
Approx. 0.5 kg (without T-type connector)
Approvals
TÜV approval acc. to VdTÜV Bulletin
"Water Monitoring 100": Requirements made on water
monitoring equipment
Type approval no. TÜV · WÜL · XX-017, XX-018.
UL/cUL (CSA) Approval: UL 508 and CSA C22.2 No. 14-13,
Standards for Industrial Control Equipment. File E243189
conductivity electrode LRG 16-4